plus minus gleich

Handheld Power Analyzer (1000)

Our Handheld meter products are used by Power Distribution companies to test commercial and residential power meters and to assure their accuracy and safety. This product is available in three modes: 100Amp, 1000Amp and 3600 Amp, based on the Clamp model used.

Features 

 

  • 3 voltage channels and 3 current channels with transformer isolation
  • Nominal Voltage for voltage channels can be either 100V or 110 V, phase to ground (can be chosen up to 230 V)
  • Nominal Current for channels is according to the used clamp Current Measurement using 1000A clamps can be done in two ranges which are from 100mA to 20A, and from 10A to 1000A Current Measurement using 3600A clamps can be done in two ranges which are from 1A to 60A, and from  30A to 3600A (Whenever the current exceeds first range, measurement enters higher range automatically; even in logging, the data will be automatically stored in the right way)
  • Sampling Period for each voltage and current channel is equal to 128μs (approximately 7 kHz)
  • 16 bit A to D IC is used
  • Real-time displaying of measured, and calculated quantities on 4×20 characters LCD display
  • Connectable to different types of distribution networks, and extra high voltage distribution networks (380V to 400kV)
  • Measurement Precision for voltages and currents is better than 0.3%
  • Capability of Logging, Event Recording, Online Trend, and Archive Trend
  • Memory backup battery works up to two years without mains power (efficient battery life line is 10 years).
  • Connects to PC via Infrared with transmission rate equal to 115200 bps
  • Power Supply can be from 80 to 250VAC, and 100 to 300VDC

 

Memory

 

The device has 64MB of Flash Memory, 33 MB of that is allocated for Log, 27MB is for Fault, and 4MB is for Event.

 

Standalone

 

The device works independent of other devices and the PC. As mentioned before
each device has a Flash Memory in which data of logs, events, faults, and other
needed data are stored. Whenever PC is on, the stored data can be read and saved by
the PC.

 

Software Upgrade

 

System Software Upgrade can be done without making any changes in the hardware.
The new software can be uploaded from the PC and via a communication link.

 

Measurable Quantities


  • Frequency
  • RMS of voltage and current
  • Active Power, Reactive Power, and Apparent Power of each phase, and for three phases together
  • Power Factor of each phase, and Total Power Factor
  • Active and Reactive Energy in 4 tariffs
  • Maximums and minimums of the quantities during averaged cycles in each storing period, which enables device to record changes that has happened even during 10ms

Recording, calculating, and displaying Power Quality Measures such as

  • Voltage and current harmonic components. They can be displayed up to 15th online (extendible to 31st), and up to 60th Offline.
  • Voltage and current unbalance percentage, short term and long term power outs, and Dips& Swells in voltage.
  • Transient Errors
  • Logging Memory is 33MB. It can for example store data of all measurable quantities (Approximately 380) for two months while sampling period is chosen as one minute

Fault Recorder Features

 

  • Capable of recording currents up to the limit of used clamp
  • Capable of recording voltages up to 250V
  • Data Storing Time Range can be up to 300ms for pre-fault, and from 1s to 100s for post-fault
  • Flash Memory Cards used which are highly reliable
  • Memory implemented in the device is able to store 200s of fault waveforms altogether (for example one hundred, two second long faults or forty, five second long faults or two, one hundred second long faults).
  • Measurement Precision Class is better than 0.5%
  • RMS voltages and currents trespassing certain threshold level can trigger Fault Recorder
  • It can be triggered due to the change in the slope of current
  • It can be triggered due to the current unbalances


Software Features

 

  • It has 8 windows which connect user to the device graphically


     Online windows
     


    - Capability of determining type of connection to the PC, and adjusting threshold levels for faults to be taken on analog inputs
    - Ability to adjust clock of the device using clock of the PC
    - Providing Fault and Internal Event Lists which contain fault or event reason, their time of occurrence up to ms, value of quantities at the time of occurrence, threshold levels at the time of occurrence, and ability to store these lists in a computer file.
    - Real-time displaying of voltage and current waveforms
    - Displaying waveforms before, and after the fault occurrence
    - Real-time displaying of voltages and currents of three phases and their average, frequency, active, reactive and apparent powers of each phase and also the total value of these powers, power factor of each phase and total power factor, THD, and odd harmonics of voltages and currents up to 9th for each phase. All these quantities will be updated every one second
    - Ability to change logging adjustments including number of quantities, recording maximums and minimums of the quantities in 10ms periods, Log Rate, Dip & Swell limits, and Storing the taken log in computer files
    - Reading Energy Information including imported and exported energy in 4 tariffs, active and reactive energy imported or exported, demand, and ability to reset demand and imported energy
    - Providing Dip & Swell Lists, and ability to save them in a computer file
    - Providing On/Off and Outage Lists which contain their occurrence time


Offline Windows

 

- Reading saved log files, and also displaying their waveforms
- Reading saved fault files and displaying polar view of voltages and currents at fault occurrence time, and displaying voltage and current harmonic components up to 60th
- Reading Energy Management information, and displaying daily energy consumption information, and daily load curve
- Ability to print information in all offline pages
- Ability to export fault, event, and log information to Excel and Delphi softwares or other databases
- Displaying Single Line Diagram

file icon pdf  Download Catalogue